| dc.description.abstract |
Radial distribution systems often operate under heavily loaded conditions, resulting in
significant power losses and poor voltage regulation. This study presents a comparative analysis
of Flexible AC Transmission System (FACTS) devices for power loss minimization and voltage
profile enhancement in a 28-bus, 33-kV radial distribution network, with specific application to
Sawla Substation Feeder II. The Backward/Forward Sweep load flow method was implemented
in MATLAB to evaluate system performance under base-case conditions and after integrating
Static VAR Compensator (SVC), Distribution STATCOM (DSTATCOM), and Unified Power
Quality Conditioner (UPQC). The assessment was based on voltage profile improvement, active
power loss reduction, and overall system performance enhancement. Base-case results showed
poor voltage regulation, with a minimum voltage of 0.9417 p.u. at Bus 28 and total active power
loss of 2.7086 MW. With SVC integration, voltage levels improved to approximately 0.95 p.u. at
weak buses, and active power loss was reduced by 7.54%, demonstrating effective shunt reactive
power compensation. DSTATCOM provided further improvement with better dynamic voltage
support at the weakest bus, achieving a 10.47% reduction in active power loss and more stable
voltage regulation across the feeder. The UPQC achieved the best overall performance,
improving voltage stability throughout the system and reducing total active power loss by
11.06%, owing to its combined series and shunt compensation capability. The study concludes
that UPQC offers superior technical performance for voltage regulation and loss minimization,
while DSTATCOM provides a strong balance between performance and practicality. SVC
remains an effective low-cost solution for basic voltage support, making it suitable for less
critical applications in radial distribution systems |