Jimma University Open access Institutional Repository

Improving Distribution Transformer Performance Through ANFIS-Based Load Balancing and Monitoring on the Low-Voltage Side: A Case Study of Shebe Distribution System, Jimma Zone

Show simple item record

dc.contributor.author Bedada Boba
dc.contributor.author Shewit Tsegaye
dc.contributor.author Marta Zemedu
dc.date.accessioned 2026-11-16T07:02:43Z
dc.date.available 2026-11-16T07:02:43Z
dc.date.issued 2025-12
dc.identifier.uri https://repository.ju.edu.et//handle/123456789/10367
dc.description.abstract A distribution transformer serves as a critical interface between the distribution network and low-voltage consumers, where unbalanced phase loading can adversely affect operational performance. In the Shebe distribution network, significant phase current disparities have led to elevated neutral currents, voltage deviations, and increased stress on transformer components, highlighting the need for an effective load balancing strategy. This study proposes an intelligent transformer load balancing and performance monitoring approach based on an Adaptive Neuro-Fuzzy Inference System (ANFIS). The ANFIS model was developed using historical and periodically recorded operational data, including phase voltages, phase currents, and load profiles, collected in collaboration with the Ethiopian Electric Utility. Simulation results obtained in MATLAB demonstrate that the proposed method achieves substantial improvements in phase current symmetry and voltage regulation while drastically reducing neutral current magnitude. Furthermore, performance evaluation metrics indicate notable reductions in load power deviation and prediction errors, as evidenced by improved normalized MAE and RMSE values. The results validate the robustness and effectiveness of the proposed ANFIS-based approach in enhancing load balance and power quality on the low-voltage side of distribution transformers. en_US
dc.language.iso en en_US
dc.subject distribution transformer; load balancing; adaptive neuro-fuzzy inference system (ANFIS); current unbalanced factor (IUF); voltage unbalanced factor (VUF); load power deviation (LPD); efficiency en_US
dc.title Improving Distribution Transformer Performance Through ANFIS-Based Load Balancing and Monitoring on the Low-Voltage Side: A Case Study of Shebe Distribution System, Jimma Zone en_US
dc.type Thesis en_US


Files in this item

This item appears in the following Collection(s)

Show simple item record

Search IR